CISA has added four Danfoss AK-SM refrigeration controller vulnerabilities to its Known Exploited Vulnerabilities catalog, including CVE-2026-129713, a critical flaw that has no patch available yet. The listings come after attacks on European supermarkets that altered refrigeration settings and spoiled food.
CVE-2026-129713 Allows Unauthenticated Code Execution on AK-SM 8xxA Controllers
CVE-2026-129713 carries a CVSS score of 9.8, or 9.3 on another scale. It is a stack-based buffer overflow in an unauthenticated CGI handler. A crafted HTTP or HTTPS POST request causes memory corruption and a web server restart, and can potentially lead to code execution with web server privileges. No authentication is needed.
The affected products are the Danfoss AK-SM 8xxA series refrigeration controllers: the 820A, 850A and 880A models.
CISA published an ICS advisory on Nov. 24 and made the KEV additions on Nov. 25. Danfoss’s own advisory, dated Nov. 20, says a fix will arrive in an “upcoming” version 5.5.x. That release will also remove the option to disable Strict mode. No patch is currently available, though Danfoss and CISA have both issued interim mitigation guidance.
Three Older AK-SM 800A Flaws Joined the Catalog
CISA also listed three earlier Danfoss AK-SM 800A vulnerabilities in KEV:
- CVE-2023-25914, a path traversal flaw rated 7.5
- CVE-2023-25915, an authenticated command injection flaw rated 9.8
- CVE-2025-41450, an authentication bypass rated 8.2, found by Claroty Team82
Danfoss does not say these three were exploited. They are likely connected to the recent supermarket attacks, though no public confirmation of that link exists. Federal agencies face a Nov. 28 deadline for most of the items and Dec. 9 for the remaining two.
The Supermarket Attacks Behind CISA’s Move
The KEV additions follow two waves of attacks on European food retail. On Oct. 11 and 12, attackers hit up to 700 French supermarket sites, including Intermarche, Carrefour Market, Leclerc and Super U. They altered defrost settings, which spoiled food. France attributed the attacks to Shahid Kaveh, an Iranian unit affiliated with the IRGC.
On Nov. 1 and 2, a second wave struck at least 115 stores in Belgium, the Netherlands, Sweden, Luxembourg, Ireland, Romania and Estonia. It also reached a refrigeration supplier to the French national blood service, affecting three facilities.
Why Refrigeration Controllers Became a Physical-World Target
The attacks changed a physical process, temperature control, rather than stealing data. The Danfoss case shows how internet-exposed operational technology can produce direct consequences for food retailers and the cold chain. The reporting does not state how the controllers were reached, and the public record does not confirm which specific flaws were used.
Mitigation While No Fix Exists
With no patch available for CVE-2026-129713, the recommended response is to apply the Danfoss mitigations and remove internet exposure of the controllers. Operators should also apply older fixes, which are versions 3.3 and 4.2 for the earlier flaws.
The scale of Danfoss AK-SM deployment worldwide is not known, so the number of exposed controllers cannot be estimated from the available reporting. Food retailers and cold chain operators are the groups identified as at risk.
The Wait for Danfoss Version 5.5.x
Danfoss has not given a date for the 5.5.x release. Until it arrives, operators depend on network-level controls rather than a code fix. The planned removal of the option to disable Strict mode indicates Danfoss intends the next release to force a stricter configuration, though the company’s advisory does not explain how that setting relates to the buffer overflow.
The combination of an unpatched critical flaw and attackers already targeting the same product family leaves operators with a shorter safe window than a routine disclosure would. The CVSS 9.8 rating reflects that no credentials are needed, and the contrast with the authenticated CVE-2023-25915 shows the newer flaw is the easier of the two to reach from the internet. France’s attribution of the October attacks to an IRGC-affiliated unit places the campaign in the category of state-linked operations against exposed industrial equipment.